TCQF 121213 Series Counterflow QUIETFLOW® Cooling Tower
The Tower Thermal TCQF-121213 Counterflow QUIETFLOW® Cooling Tower Series combines induced-draft evaporative cooling with a 1,200 × 1,200 mm plan footprint. Choose a 1.5 kW or 2.2 kW fan motor and either AS stainless steel or AG hot-dip galvanised steel construction for commercial HVAC condenser water and industrial process cooling applications.
Vertical Counterflow Cooling
Air is drawn upward through the heat transfer fill while warm water travels downward. The opposing air and water flows support evaporative heat rejection before cooled water returns to the connected system.
AS Stainless Steel and AG Galvanised Steel Options
- AS — Stainless steel: Stainless steel casing, basin, structural members and hardware.
- AG — Hot-dip galvanised steel: Galvanised casing, basin, structural members and hardware.
Both options use steel enclosure and structural components. Select the construction material to suit the site's environment, water chemistry and treatment programme.
Motor Options and Published Water Flow
| Base model | Fan motor power | Published water flow |
|---|---|---|
| TCQF-121213-15 | 1.5 kW | 10.2 L/s |
| TCQF-121213-22 | 2.2 kW | 11.8 L/s |
Published flows are based on 35°C entering water, 29.5°C leaving water and 22°C ambient wet-bulb temperature. Fan motor power is electrical power, not thermal cooling capacity. Tower selection must be checked against the actual project duty and operating conditions.
Overall Dimensions and Maintenance Access
The TCQF-121213 measures 1,200 mm long × 1,200 mm wide × 4,466 mm high. Its model drawing shows a rear access door, DN100 water inlet and outlet, and basin make-up, overflow and drain connections.
Keep the space above the fan discharge unobstructed. Provide maintenance access and confirm operating loads, support requirements and connection positions against the approved project drawings.
Drive and Accessory Options
The CTI disclosure specifies standard belt drive with optional gear drive. It also includes optional handrails, caged ladders, external louvres in place of standard cellular louvres, and a super-low-noise fan option identified by the /SLF suffix. Confirm the required accessories and drive arrangement with Tower Thermal.
CTI Model Listing
The TCQF-121213-15 and TCQF-121213-22 base models are listed in the supplied TCQF CTI certification disclosure, validation number C27G-20R01, revision 1 dated 1 May 2026. The construction notes define both AS and AG material options.
Request a TCQF-121213 Cooling Tower Quote
Contact Tower Thermal with your required cooling duty, circulating water flow, entering and leaving water temperatures, design wet-bulb temperature, water quality and available plant space. Our team can help select the motor rating, construction material and accessories for your installation.
| SKU | TCQF-121213 |
| Brand | TCQF |
| Assembled Length | 1.200m |
| Assembled Height | 4.466m |
| Assembled Width | 1.200m |