The Case

Cooling towers had a lot of bad press some years ago and no wonder with all the outbreaks of Legionnaires’ disease going on. There have been all sorts of arguments and theories about the reasons for these outbreaks, new regulations have been brought in and new water treatment systems have come onto the market to improve water quality in cooling towers. Sure, all these recent fixes have made a difference, but they are all add on solutions, IE, accessories to the cooling tower rather than any major changes to the cooling tower itself.  

History

Let’s go back in time to investigate at what turning point in history did cooling towers lose favour with public opinion.

In the last 15 years or so, how many Legionnaires’ disease outbreaks in Victoria were attributable to crossflow towers? Statistical data on this subject is not available, however, my limited observation of reported outbreaks indicate that very few were caused by crossflow towers. The main offenders appear to be counterflow towers. There are also different types of counterflow towers; induced draft, forced draft, etc. and some types may be safer than others. However, the induced draft type has had the greatest proliferation in recent years.

It is important to note that I am referring to Legionnaires’ disease, not Legionella detected in cooling tower basins. There is a difference between detection within a tower and the micro-organism escaping from the tower. If it can’t escape, then its presence is harmless.

Operational influences and market forces have caused cooling tower design  to evolve and this paper compares the 2 different configurations, both of which  utilize modern, PVC, film fill.

Principles of Operation

The basic difference between crossflow and counterflow is the contact angle of the air and water mixture at the point of primary heat exchange, the fill surface.

Crossflow cooling towers have a 90 degree contact angle of air and water mixture. Air is drawn horizontally across a fill pack while water flows down vertically from the top.

Counterflow cooling towers have a 180 degree contact angle of air and water mixture. Air moves up vertically through the fill pack while water flows down vertically in the opposite direction.

Counterflow Design

Induced draft counterflow towers gained immense popularity since the early 90’s in the race for lower pricing as their design and construction is generally lower in cost to crossflows. New tower installations became dominated by counterflow and many older style, crossflow tower configurations were converted to counterflow when replaced. This trend still continues today.

The counterflow’s smaller plan area is favoured by consulting engineers and architects as it saves on valuable building space. However, the race to provide a lower priced product in a smaller package may have come at a cost to the community with the increase in the incidences of Legionnaires’ disease, peaking around the late 90’s, early 00’s. New regulations have since reduced this incidence.

Associated with the induced draft counterflow tower revolution came higher pressure sprays which by nature create aerosols via more efficient atomization of the inlet water; higher internal air velocities more efficient at dragging smaller water droplets off the fill and off the sprays and through the eliminators; water distribution systems that are directly in the air stream; nozzles located closer to the eliminators due to a more compact design; crossfluted fill sheets which have many intersections that can retain more dirt and bacteria in the fill pack and let’s not forget another area of drift creation, the splash or rain zone under the fill.

Windage

The rain zone is the where the water falls out of the fill, which is suspended above the water line and then splashes into the basin below. This splashing creates aerosols which can be blown out through the louvres and carried away by prevailing winds in outdoor towers. This kind of drift is known as windage. It is interesting to note that counterflow towers are not required to have drift eliminators fitted at this location. Recent improvements by some manufacturers have seen double thickness louvre grilles fitted, however most are thin grilles or open type louvres.

Water Consumption

Water consumption is a topical issue at the moment and windage can add to the overall water lost from a counterflow tower. Look for a wet area around the tower. The larger the tower, the worse the condition can be, especially on large industrial “louvreless” designs.

Noise 

Another undesirable by-product of the rain zone is additional ground based noise (water fall effect). On large industrial counterflow towers, this high frequency nuisance noise can be heard over the fan noise at close proximity and continues when the fan cycles off, thereby diminishing noise savings via use of VSD’s.

Power Consumption

Generally, packaged cooling towers used for HVAC applications are about equal in fan power requirements regardless of the configuration. However, there can be a difference when it comes to pump head as the counterflow tower requires pressure to operate its nozzles, therefore consuming pump power to achieve this.

When it comes to large industrial cooling towers, the gap widens as the trend in crossflow towers is for lower, wider towers with large fans. Generally, a modern, crossflow tower of latest design will have lower fan power and lower pump power due to lower static lift and lower dynamic inlet pressures.

Operation and Maintenance

The counterflow design raises issues with difficulty of access to some major components. Blocked nozzles can’t be serviced without shutting down the tower or cell. This is a particularly big problem with large industrial towers which can suffer from pipe scale blockages and blown out nozzle diffuser plates. This reduces performance and plant production and leads to a premature plant shut-down while the tower nozzles are cleaned. Cleaning requires confined space access and crawling on the top of the fill, potentially damaging it without placement of protective boards.

It is arguable whether multi-layered, crossflute structured counterflow fill can be properly cleaned without removal. Even so, it is certainly fully encased in the tower making access rather difficult and cumbersome. Similarly for the drift eliminators.

Crossflow Design

By comparison, a properly designed, modern crossflow tower with PVC film fill does not share these similar traits. Water is distributed via covered, hot water basins with gravity flow nozzles where water is broken up, but not sprayed; air velocities across the fill are generally lower and have less effect on the water as the water distribution system is not in the air stream; nozzles are further away from the eliminators; fill sheets are parallel path with a continuous vertical void space, there are minimal snag points for dirt build up; fill extends all the way into the water line so there is a gentle transition of water into the basin, no violent splashing or water noise; and air plenums are wide, governed normally by the fan diameter, and requiring drift droplets to travel further to escape the tower.

Nozzles can be accessed and cleaned without stopping the tower by lifting the hot water basin covers. No confined space access is required.

Fill can be cleaned in-situ as the front and rear of the pack is openly accessible without removal. This is made easier with a vertical void space fill that can be accessed or spray cleaned between sheets.

Modern crossflows are fitted with internal walkways allowing walk in entry and easy access to drift eliminators.

Drift

AS 3666 specifies a maximum drift rate of 0.002% of flowrate. This is a volumetric measurement, but it is not specific to droplet size, so it can be deceiving. Smaller droplets pose a greater threat than larger droplets as they can travel further in the atmosphere and can be inhaled easier. So two cooling towers, both offering less than 0.002% drift rate, may appear of equal specification, but be very different in the creation of droplet size and numbers and hence the level of risk to the community.

Well designed large, industrial class counterflow towers have working air plenums (the gap between the eliminators and the fan deck) which are typically around 2 m in height. Smaller, packaged, HVAC counterflows have virtually no air plenum. A cost saving no doubt, but at the expense of air distribution resulting in increased “coring” potential at the eliminators – where air velocity is higher in the centre than at the perimeter of the eliminators. While “coring” may not effect the overall drift rate of a tower, it may have a greater influence on the smaller micronage droplets in the areas of higher air velocity by entraining more of this size in the discharge air.

Conclusion

Crossflow towers may be a safer and more environmentally friendly alternative, although more studies still need to be done to prove this theory.

Like it or not, Legionella has always lived in cooling towers at some time or another, but nowadays we may be doing a better job of expelling it rather than confining it to just the tower. There are certainly many other contributing factors that lead to incidences of Legionnaires’ disease and this paper is an attempt to explore just one of the many possible scenarios.

Now with the addition of new environmental considerations of water, power and noise, cooling tower designers may need to smarten up their act or market pressure will prevail upon new evidence and cooling tower design will be forced  to evolve yet again.

The comments provided herein are theories and opinions of the author and may vary to actual, individual situations.

Steven Teleki  GradDipEng

Applications Engineer

Tower Thermal

txc crossflow cooling tower

The Crossflow Advantage

Do you buy a crossflow tower with lots of usable features or a cheap airconditioning counterflow tower with maybe a cheap price. Consider the advantages of crossflow.

With A Typical Crossflow Cooling Tower with Film Fill

Lower clog fill, vertical void space (not cross-fluted packs).  

Easily clean gravity nozzles on the run – (no stopping as for counterflow sprays).

Access basin, fill & DE’s without stopping or dismantling tower, via door & internal walkway

Reduced water atomisation into aerosols due to no pressure sprays (unlike counterflows).

Quieter as no splash zone under fill means no water noise (unlike counterflows).

Large basin volume to aid filling of overhead pipework and reduce pump cavitation.

Lower height is less obtrusive and fill is accessible without panel removal.

Lower water consumption as no rain zone under fill means reduced splash out or windage. 

Lower pump head due to gravity nozzles reduces pump power consumption. 

More, just ask.

Plus Tower Thermal Crossflow TXQ Features:

Fill sheets individually suspended & accessible (not glued, cross-fluted packs).

■ Low noise, Quietflow® fan runs at low rpm, plus no splash noise as fill extends to floor.

ImpactDeck® water diffuser for superior distribution & performance at a range of flows.

Super low drift rate via double layer drift reducer fitted on TXQ-275 models & up.

Designed, engineered & QA assembled in Australia to AS3666, AS3500, AS1657.

A practical and desirable, industrial class cooling tower, not an airconditioning tower.

It is thought that properly designed crossflow towers may reduce the escape of Legionella from cooling towers into the atmosphere when compared to counterflow towers, although more research into this theory is required for conclusive proof. Some discussion papers are available on request that further detail this theory.